FXP1500-32G AC-DC Front-End
& FXR-3-32G Power Shelf Data Sheet
Safety Specifications
Maximum electric strength testing is performed in the factory according to EN 550116, IEC/EN60950-1 2 nd ed., and
UL/CSA60950-1 2 nd ed. Input-to-output electric strength tests should not be repeated in the field. Power-One will not
honor any warranty claims resulting from electric strength field tests.
Parameter
Conditions/description
Min
Nom
Max
Unit
UL/CSA60950-1 2
ed., EN60950-1 2
ed., IEC60950-1 2 ed.,
Agency approvals
nd
nd
nd
CE Mark for LVD
Insulation safety rating
Input to case
Input to output
Output to case
Basic
Reinforced
F unctiona l
Electric strength test voltage
Input to case
Input to output
Output to case
Output 1 to output 2
2.12
Note 1
0.1
0.1
kVDC
kVDC
kVDC
kVDC
1
Subassemblies are pre-tested with 4.2 kVDC in accordance with EN50116 and IEC/EN60950-1 2
nd
ed.
EMC Specification
Parameter
Electrostatic discharge
Electromagnetic field
Electrical fast transients/burst
Surge
Voltage dips and interruptions
Description
IEC/EN 61000-4-2, level 4 (contact/air)
IEC/EN 61000-4-3, level 3
IEC/EN 61000-4-4, level 3 (L/L, L/E)
IEC/EN 61000-4-5, level 3 (L/L, L/E)
IEC/EN 61000-4-11
Dip 30 %, 100 ms
Dip 30 %, 200 ms
Criterion
8/15 kV, Performance criterion B
10 V/m, Performance criterion A
2 / 1 kV, Performance criterion B
1 / 2 kV, Performance criterion B
Performance criterion A
Performance criterion B
Dip 60 %,
20 ms
Performance criterion A
Dip 60 %, 100 ms
Dip > 95 %, 20 ms
Dip > 95 %, 100 ms
Performance criterion B
Performance criterion A
Performance criterion B
RF conducted immunity
Emissions conducted
Emissions radiated
Harmonics
Voltage fluctuation and flicker
Voltage sag
IEC/EN 61000-4-6
CISPR 22/EN 55022/EN 61204
CISPR 22/EN 55022/EN 61204
IEC/EN 61000-3-2
IEC/EN 61000-3-3
SEMI F47-0200 (High Line 230V)
10 VAC, AM 80 %, 1 kHz
Performance criterion A
Class B
Class A
Class B
Pass
Pass
Input Specification
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Input voltage
Input frequency
Turn-on input voltage
Turn-off input voltage
Conditions/description
Ramping up
Ramping down
Min
85
47
79
70
Nom
230
50/60
-
-
Max
264
63
85
78
Unit
VAC
Hz
VAC
VAC
Inrush current limitation
115/230 VAC acc. ETS 300 132-1
< 100 ms
50
A pk
Hold-up time
Power factor
After last AC line peak , V i = 230 VAC, P o nom
V i nom , I o nom
20
0.95
ms
W/VA
Efficiency
Max input current
BCD.00021 Rev.AA, 31-JAN -11
V i = 230 VAC, V o nom , I o nom , T c =25 °C
Page 3 of 16
89
89.5
%
20
A rms